Event data logger
Four-channel data logger is designed for record of two-state events. Values are stored to a non volatile electronic memory. Data transfer to the personal computer for further analysis is performed via USB, RS232, GSM or Ethernet interface by means of a proper communication adapter.
The device includes Traceable calibration certificate with declared metrological traceability of etalons is based on requirements of EN ISO/IEC 17025 standard.
For communication with the PC must be from Optional accessories ordered USB adapter or COM adapter or start/stop magnet if is needed to control logging the other way than directly from computer.
-
codeS7841
-
Warranty3 years
- On request
Technical data
BINARY INPUT
Vstupní signály
from potential - less contact or two - state voltage signal
Terminal block input signals
removable WAGO 734, Maximum lead cross section 1.5 mm2
Connector for connection of input signals
CYESN 9 pins
GENERAL TECHNICAL DATA
Operating temperature
-30 to +70 °C
Channels
4x binary input
Memory
16,000 values
Recording interval
adjustable from 10 s to 24 h
Display and alarm refresh
each 5 s
Recording mode
noncyclic - data logging stops after filling the memory
cyclic - after filling memory oldest data is overwritten by new
cyclic - after filling memory oldest data is overwritten by new
Real time clock
year, leap year, month, day, hour, minute, second
Power
lithium battery 3.6 V; size AA
Battery life
5 years
Protection class
IP20
Dimensions (without connectors)
93 x 64 x 29 mm
Weight (including batteries)
approx. 115 g
Warranty