Dual channel logger with pulse and binary input
Data logger is designed for record of pulses and two-state events. Values are stored to a non volatile electronic memory. Data transfer to the personal computer for further analysis is performed via USB, RS232, GSM or Ethernet interface by means of a proper communication adapter.
The device includes Traceable calibration certificate with declared metrological traceability of etalons is based on requirements of EN ISO/IEC 17025 standard.
For communication with the PC must be from Optional accessories ordered USB adapter or COM adapter or start/stop magnet if is needed to control logging the other way than directly from computer.
-
codeS7021
-
Warranty3 years
- On request
Technical data
COUNTER INPUT
Counter range
in 16 bits mode 0 to 61 695 values
in 32 bits mode 0 to 2 021 654 527 values
in 32 bits mode 0 to 2 021 654 527 values
Signal for binary input
from potential - less contact or two - state voltage signal
Minimum pulse duration at counter input:
1 ms (shorter pulses may not be recorded)
Maximum frequency on binary input
500 Hz
Current through closed contact
30 µA
Voltage across open contact
max 3.6 V
LOW voltage level on binary input
0 to +0,2 V (proud ze vstupu max. 30 µA)
HIGH voltage level on binary input
+3 to +30 V, current to input max. 100 nA
Connector for connection of input signals
CYESN 9 pins
BINARY INPUT
Minimum pulse duration on binary input
500 ms (shorter pulses will not be recorded)
Maximum frequency on binary input
0,5 Hz (i.e maximum of 5 pulses for 10 s)
Power current of connected contact
3 µA (contact closed)
Voltage across open contact
max 3.6 V
LOW voltage level on binary input
0 to +0.2 V, current from input max. 3 µA
HIGH voltage level on binary input
+3 to +30 V, current to input max. 100 nA
Connector for connection of input signals
CYESN 9 pins
GENERAL TECHNICAL DATA
Operating temperature
-30 to +70 °C
Channels
1x counter, 1x binary input
Memory
32,000 values
Recording interval
adjustable from 10 s to 24 h
Display and alarm refresh
each 10 s
Recording mode
noncyclic - data logging stops after filling the memory
cyclic - after filling memory oldest data is overwritten by new
cyclic - after filling memory oldest data is overwritten by new
Real time clock
year, leap year, month, day, hour, minute, second
Power
lithium battery 3.6 V; size AA
Battery life
5 years
Protection class
IP67
Dimensions (without connectors)
93 x 64 x 29 mm
Weight (including batteries)
approx. 115 g
Warranty
3 years